Übersetzen...
101

PID Feedback Supervision Fault (PID1)

Vacon · 100 FLOW Application Guide

Was bedeutet 101 ?

The feedback value for PID controller 1 is outside the configured supervision limits (P3.13.6.2 and P3.13.6.3) for a specified delay (P3.13.6.4). This indicates a deviation from the expected process variable feedback, suggesting an issue with the process or the sensor. It can lead to incorrect control actions and process instability.

Häufige Ursachen

  • Malfunctioning process sensor providing feedback to PID controller 1 (e.g., pressure, flow, level sensor) causing an out-of-range signal.
  • Feedback signal cable from the sensor to the drive's analog input (e.g., AI1) is damaged, disconnected, or experiencing high noise.
  • PID supervision limits (P3.13.6.2 for low limit, P3.13.6.3 for high limit) are set too tightly for the process's normal operating range or expected transients.
  • The process being controlled by PID1 is experiencing a severe disturbance (e.g., pump cavitation, valve blockage) leading to a significant feedback deviation.
  • The delay time for supervision (P3.13.6.4) is set too short, causing the fault to trigger prematurely during acceptable process fluctuations.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Verify the physical process feedback signal at the assigned analog input terminal (e.g., AI1) using a multimeter, comparing it to the actual process variable reading.

  2. 2

    2. Inspect the wiring from the process sensor to the drive's analog input for continuity, proper shielding, and secure connections.

  3. 3

    3. Check the process sensor itself for proper operation, including its power supply, output range, and calibration.

  4. 4

    4. Review and adjust the PID feedback supervision parameters: P3.13.6.2 (low limit), P3.13.6.3 (high limit), and P3.13.6.4 (delay time) to match the process's expected behavior.

  5. 5

    5. Observe the controlled process for any abnormal conditions (e.g., blockages, mechanical failures) that could cause the feedback deviation.

  6. 6

    6. Ensure the analog input scaling (e.g., P3.3.1.2 for min value, P3.3.1.3 for max value) for the feedback signal is correctly configured.

Alle Codes in diesem Handbuch durchsuchen (73)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Vacon 100 FLOW Application Guide