Übersetzen...
15

Motor stalled

Vacon · NX All-in-One Application

Was bedeutet 15 ?

The motor has stalled, meaning it is commanded to run but is not rotating, or its speed is significantly below commanded speed due to excessive load. This can result from mechanical binding, an overloaded application, or an issue within the motor itself. Sustained stalling can cause severe motor overheating and damage.

Häufige Ursachen

  • Motor is unable to rotate or is rotating too slowly under load.
  • Mechanical jamming or excessive friction in the driven equipment.
  • Motor torque is insufficient to overcome the load.
  • Incorrect motor parameters or tuning (e.g., P3-xx, P2-xx).
  • Low motor voltage or phase loss.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Visually inspect the motor and its connected mechanical load for any obstructions, seized bearings, or binding points that prevent rotation.

  2. 2

    Verify the integrity of the motor's mechanical coupling to the load — check for shear pins, broken shafts, or loose connections.

  3. 3

    Monitor the motor's current draw during an attempted start or run cycle — compare it to the motor's nameplate Full Load Amps (FLA) and the drive's current limit settings.

Alle Codes in diesem Handbuch durchsuchen (42)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Vacon NX All-in-One Application