Motor underload
Vacon · NX All-in-One Application
Was bedeutet 17 ?
The motor underload protection has tripped, indicating that the motor's current draw is significantly lower than expected given its operating conditions and commanded speed. This typically suggests a loss of mechanical load, a broken coupling, or an issue with the driven equipment. Running under severe underload can sometimes lead to inefficient operation or potential runaway conditions in certain applications.
Häufige Ursachen
- Motor is drawing significantly less current than expected for the operating conditions.
- Mechanical load is too light or absent.
- Incorrect motor parameters leading to under-estimation of required torque.
- Encoder feedback suggesting no load when one exists.
- Minimum torque setting too low.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect the mechanical load connected to the motor — confirm it is present and properly engaged with the motor shaft.
- 2
Check for any broken belts, damaged couplings, or other mechanical failures that would cause the motor to lose its intended load.
- 3
Verify the motor's current draw against the expected current for the application and the drive's underload threshold settings.