Übersetzen...
59

Follower Communication Fault

Vacon · NX All-in-One Application

Was bedeutet 59 ?

Communication between the Master and Follower drives has been lost via SystemBus or CAN. This indicates a broken communication link, preventing coordinated operation between the units.

Häufige Ursachen

  • Communication failure between a master and a follower drive/device.
  • Incorrect follower address or configuration (e.g., P9-01).
  • Network cabling issue between devices.
  • Follower device powered off or not initialized.
  • Data corruption during follower communication.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the option board parameters related to SystemBus or CAN communication for correct configuration (e.g., node ID, baud rate).

  2. 2

    Inspect the optical fibre cable or CAN cable for physical damage, proper connections, and correct termination between master and follower drives.

Alle Codes in diesem Handbuch durchsuchen (42)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Vacon NX All-in-One Application