Earth Fault

Vacon · NX Liquid-Cooled Drive

Was bedeutet 3 ?

The current measurement system has detected that the sum of the motor phase currents is not zero, indicating a leakage current to ground. This fault is most commonly caused by insulation failure in the motor cables or within the motor windings themselves.

Häufige Ursachen

  • Insulation failure in motor windings or power cables.
  • Ground fault in the connected equipment.
  • Moisture or contamination ingress into electrical components.
  • Faulty grounding connection.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the insulation resistance between each motor phase cable (U, V, W) and ground (PE) using a megger.

  2. 2

    Measure the insulation resistance between each motor winding (U, V, W) and the motor frame (PE) with a megger.