Übersetzen...
11

Output phase supervision

Vacon · NXP/C

Was bedeutet 11 ?

The current measurement system has detected that there is no current flowing in one of the motor phases. This typically indicates an open circuit condition in the motor cables or within the motor windings, which can lead to motor damage or uncontrolled operation.

Häufige Ursachen

  • One or more output phases are open or shorted.
  • Uneven phase current distribution (P1-04, P1-05).
  • Faulty output transistors (IGBTs) in the inverter stage.
  • Motor winding insulation breakdown.
  • Incorrect motor connection to output terminals.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check all physical connections and the integrity of the motor cables between the frequency converter's output terminals (U, V, W) and the motor's input terminals.

  2. 2

    Perform a winding resistance test on the motor phases (U-V, V-W, U-W) to check for open circuits or abnormally high resistance windings.

  3. 3

    Perform an insulation resistance test (megger test) between each motor phase and the motor frame to check for ground faults.

Alle Codes in diesem Handbuch durchsuchen (11)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes