Übersetzen...
18

Unbalance

Vacon · NXS NXP

Was bedeutet 18 ?

An unbalance has been detected between power modules within paralleled power units. This signifies a discrepancy in current sharing or performance among the modules, which can lead to uneven wear and a reduced lifespan of the power components. If persistent, this fault indicates an internal issue within the paralleled power system.

Häufige Ursachen

  • Uneven impedance or resistance in output cabling (U, V, W) between parallel power modules and the common motor.
  • Faulty current sensor or measurement circuit within one of the paralleled power modules causing inaccurate current feedback.
  • Mismatched firmware versions or parameter settings (e.g., P5-10 "Parallel control mode") between the paralleled power modules.
  • Degradation or failure of switching components (IGBTs) in one power module, leading to poor current regulation.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify uniform length and gauge of output cables (U, V, W) from each power module to the common motor connection point.

  2. 2

    Check for loose or corroded connections on output terminals (U, V, W) and input terminals (R, S, T) of each power module.

  3. 3

    Compare current feedback values (e.g., P0-01) from each individual power module using a multimeter with a current clamp or through the drive's display.

  4. 4

    Confirm all paralleled power modules have identical firmware versions and critical parallel control parameters (e.g., P5-10, P5-11, P5-12) are correctly configured.

  5. 5

    Isolate each power module, if possible, and run independently to identify which module exhibits abnormal current draw or output.

Alle Codes in diesem Handbuch durchsuchen (54)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes