Emergency stop
Vacon · NXS NXP
Was bedeutet 63 ?
An emergency stop command has been received by the drive from either a digital input or via the fieldbus, resulting in an immediate halt of operation. This is a critical safety function that stops the machinery in an emergency. The drive will not accept a new run command until the fault is reset and the emergency stop condition is completely cleared.
Häufige Ursachen
- Emergency Stop pushbutton activated, opening the safety circuit and removing the 'Run Enable' signal.
- External safety device (e.g., light curtain, safety gate switch) tripped, activating the E-stop circuit.
- Fieldbus E-stop command (e.g., specific bit in control word) sent by PLC/controller due to an external system fault.
- Wiring fault in the E-stop circuit causing an unintended open circuit condition at a safety input.
- Drive internal safety monitoring system (e.g., STO) detected an issue and triggered an E-stop.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Inspect all Emergency Stop pushbuttons and external safety devices (e.g., safety mats, light curtains) for activation.
- 2
Measure continuity across the E-stop circuit (e.g., via safety relay contacts) to identify the open point.
- 3
Monitor fieldbus control word from the PLC/controller to confirm E-stop command (e.g., bit 10 in control word 1) is not active.
- 4
Verify voltage at the drive's safety input terminals (e.g., terminals 37 and 38 for STO) for required 24VDC.
- 5
Reset any tripped safety relays or re-engage safety devices and confirm their status indicator lights (e.g., green LED).
- 6
Check drive's event log for specific E-stop source (e.g., 'DI 18 - E-stop activated').