Übersetzen...
64

Input switch open

Vacon · NXS NXP

Was bedeutet 64 ?

The main input power switch for the drive is detected as open, preventing power from reaching the drive and making it inoperable. This could refer to a physical disconnect switch, a tripped circuit breaker, or an internal contactor. The drive cannot function without incoming power.

Häufige Ursachen

  • Main circuit breaker (e.g., Q1) upstream of the drive is tripped or intentionally switched off.
  • Main disconnect switch (e.g., DS1) feeding the drive is open.
  • Fuse failure in the input power line to the drive (e.g., L1, L2, L3).
  • Internal power contactor (if present) failed to close or its auxiliary contacts are faulty.
  • Drive's internal input voltage monitoring circuit (e.g., over/under voltage detection) is faulty or miscalibrated.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the main circuit breaker (e.g., Q1) feeding the drive is in the 'ON' position and not tripped.

  2. 2

    Confirm the main disconnect switch (e.g., DS1) to the drive is closed and locked out (LOTO).

  3. 3

    Measure line voltage at the drive input terminals (e.g., R, S, T) (should be 400VAC or 480VAC) using a true-RMS multimeter.

  4. 4

    Check continuity of input fuses (if present) using a multimeter.

  5. 5

    Inspect any upstream power contactors or auxiliary contacts for proper operation and connection.

  6. 6

    Review the drive's event log for any related under-voltage or phase loss fault codes.

Alle Codes in diesem Handbuch durchsuchen (54)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes