Übersetzen...
74

Follower fault

Vacon · NXS NXP

Was bedeutet 74 ?

In a Master-Follower configuration, this fault code is generated when one or more of the follower drives trip into a fault state. This indicates an underlying issue with a specific follower drive, which then propagates to the master. The master cannot resume normal operation until the root fault on the follower drive(s) is identified and resolved.

Häufige Ursachen

  • One of the follower drives has experienced an internal fault (e.g., overcurrent, overvoltage, motor overload) independent of the master.
  • Communication loss to a specific follower drive, causing it to fault out (e.g., similar to Code 59).
  • Mechanical issue on the follower's motor or load, causing it to draw excessive current or stall.
  • Incorrect configuration of a follower drive parameter (e.g., P1-01 for motor power, P1-02 for motor voltage) leading to individual fault.
  • Power supply issue to one of the follower drives (e.g., phase loss, undervoltage).

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Identify the specific follower drive that is reporting the fault by checking its local display or error log.

  2. 2

    Access the identified follower drive's fault history or status screen to determine the specific fault code (e.g., Code 11 Overcurrent).

  3. 3

    Check the power supply (e.g., R, S, T terminals) to the faulty follower drive using a multimeter for correct voltage and phase presence.

  4. 4

    Verify communication status (e.g., activity LEDs) on the faulty follower drive's communication option board.

  5. 5

    Inspect the motor and mechanical load connected to the faulty follower drive for any mechanical binding or obstruction.

  6. 6

    Compare key operating parameters (e.g., P1-01, P1-02, P1-03) of the faulty follower drive with a working follower drive for discrepancies.

Alle Codes in diesem Handbuch durchsuchen (54)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes