19

Over-temperature Condition (Control Board Thermistor Fault, Adv. Code 3)

Vacon · X4

Was bedeutet 19 ?

This fault indicates a problem with the control board temperature sensor (thermistor) or its connection. The drive cannot accurately monitor the control board temperature, which could lead to undetected overheating and damage to critical control components. This compromises the drive's ability to protect itself.

Häufige Ursachen

  • Control board thermistor open-circuited or short-circuited due to physical damage or manufacturing defect, providing incorrect temperature readings.
  • Loose or corroded connector for the control board thermistor, leading to an intermittent or incorrect resistance reading.
  • Ambient temperature inside the control panel or around the drive's control board exceeding the specified operating limits (e.g., >50°C).
  • Poor airflow around the control board due to clogged vent holes or internal fan failure affecting control board cooling.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Power down. Visually inspect the control board for any physical damage, burnt components, or loose ribbon cable connections.

  2. 2

    2. Locate the control board thermistor (refer to drive manual for exact location) and verify its connections are secure.

  3. 3

    3. Measure the ambient temperature immediately surrounding the control board using a calibrated thermometer.

  4. 4

    4. If possible and safe, measure the resistance of the thermistor directly (requires knowing expected resistance values at room temperature). An open circuit or dead short indicates sensor failure.

  5. 5

    5. Ensure all drive internal fans are operational and not obstructed, providing adequate airflow to the control board area.

Alle Codes in diesem Handbuch durchsuchen (33)