Übersetzen...
EF8

External Fault

Yaskawa · Drive Fault Codes

Was bedeutet EF8 ?

An external fault detected by the drive, signaling an issue with a device connected to the external fault input terminals, specifically S1. The fault code (EF0-EF8) may indicate different external fault conditions defined by the user or manufacturer.

Häufige Ursachen

  • Fault condition from an external safety device (e.g., thermal overload, emergency stop switch, limit switch)
  • Incorrect wiring or loose connection to the S1 terminal, leading to an unintended fault signal
  • Faulty external sensor or switch providing the fault signal to the drive.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect all external devices connected to the S1 terminal for their operational status and reset any tripped devices.

  2. 2

    Verify the integrity of wiring connections to the S1 terminal and check for continuity.

  3. 3

    Measure the voltage signal at the S1 terminal to ensure it is within the expected range (e.g., 24VDC when the fault is clear).

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes