Was bedeutet CE ?

This fault indicates a loss of serial communication (e.g., Modbus) between the drive and its control system for more than 2 seconds, affecting parameters like H5-04 and H5-05. The drive will execute a programmed stopping method, becoming unresponsive to external commands. Prolonged communication loss can lead to process interruption and potential safety hazards if the drive is not properly controlled.

Häufige Ursachen

  • Loss of communication from the master controller (e.g., PLC, HMI) to the drive, due to a program stop, power loss, or communication port failure on the master.
  • Intermittent or broken network cable connection between the drive and the master, causing data packets to be lost or corrupted.
  • Incorrectly configured communication timeout settings (e.g., H5-04 Communication Timeout Detection Time, H5-05 Communication Timeout Action) in the drive.
  • Excessive network traffic, latency, or bus contention preventing the drive from receiving a valid command within the timeout period.
  • Incorrect network address (H5-02) for the drive, causing the master to send commands to the wrong device or the drive to ignore incoming messages.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the operational status of the master controller (PLC/HMI) and its communication port, ensuring it is powered on and actively sending commands to the drive.

  2. 2

    Inspect the network cable and connectors between the drive and the master for physical damage, looseness, or intermittence, using a cable tester if available.

  3. 3

    Adjust parameter H5-04 (Communication Timeout Detection Time) to a longer duration (e.g., 5-10 seconds) to account for expected network latency or intermittent traffic.

  4. 4

    Confirm that parameter H5-02 (Communication Node Address) on the drive matches the address configured in the master controller's communication settings.

  5. 5

    Use network diagnostic tools to monitor the serial communication bus (e.g., Modbus RTU traffic) for errors, delays, or periods of inactivity from the master.