Loss of Prime Fault
Yaskawa · iQpump Simplex Pump Drive
Was bedeutet LOP ?
The iQpump has detected a loss of prime condition within the pump. This fault occurs when the output current drops below the level set in parameter P1-14, while the output frequency is at its maximum. This condition must persist for the time specified in parameter P1-12 before the iQpump triggers the fault and coasts to a stop.
Häufige Ursachen
- Output current dropping below the P1-14 (Prime Loss Level) threshold due to lack of water.
- Pump operating at maximum output frequency (e.g., 60 Hz) while drawing very low current.
- Insufficient water supply to the pump suction inlet.
- Air ingress into the pump casing or suction line.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify parameter P1-14 (Prime Loss Level) is set correctly based on the pump's no-load or dry-run current.
- 2
Verify parameter P1-12 (Not Maintaining Set-Point Delay Time) is appropriate for detecting a sustained low-current condition.
- 3
Check the pump's suction line, foot valve, and impeller for blockages, air leaks, or damage.
- 4
Ensure the water source is adequate and the pump has been properly primed (filled with liquid).