dnE
Drive Disabled
Yaskawa · iQpump1000
Was bedeutet dnE ?
The drive is disabled because the 'Drive Enable' function is configured to a multi-function contact input (parameter H1-OO = 6A), and this contact is currently open. This prevents the drive from operating, potentially indicating an improper control sequence.
Häufige Ursachen
- The multi-function contact input configured for Drive Enable (H1-OO = 6A) is open
- Improper operation sequence of the Drive Enable command from the control system
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify the physical state of the multi-function contact input configured as Drive Enable (parameter H1-OO = 6A).
- 2
Ensure the Drive Enable contact input is closed to enable drive operation.
- 3
Review the overall control system operation sequence to confirm correct timing and logic for the Drive Enable command.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026