Übersetzen...
LOWWL
Low Water Level
Yaskawa · iQpump1000
Was bedeutet LOWWL ?
The water level has fallen below the level set in Q4-09 for longer than the time set in Q4-10. This fault is effective only when Q4-11 (Low Level Behavior) is set to 2 (fault).
Häufige Ursachen
- The water level has fallen below the configured threshold.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Raise the water level.
- 2
Set the Low Water Level fault characteristics using parameters Q4-09 and Q4-10.
- 3
Control drive response to this condition using Q4-11 (Low Level Behavior).
- 4
Control auto-restart of this fault using Q4-11 (Low Level Behavior) and Q4-12 (Water Level Control Auto-restart Time).
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026
Verwandte Fehlercodes
Quelle: Yaskawa iQpump1000