Thermistor Disconnect
Yaskawa · J1000
Was bedeutet THo ?
The thermistor used to detect motor temperature has become disconnected. This prevents the drive from accurately monitoring motor temperature, posing a significant risk of motor overheating and damage if the condition is not resolved.
Häufige Ursachen
- Motor thermistor wiring broken or disconnected between the motor and the drive's input terminals.
- Loose terminal connections at either the motor junction box or the drive's thermistor input terminals (e.g., TH1/TH2).
- The thermistor sensor itself has failed, creating an open circuit.
- Incorrect thermistor type or input configuration selected in the drive's parameters (e.g., L1-01 for thermistor input selection).
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
1. Verify continuity of the thermistor wiring from the motor junction box to the drive input terminals (e.g., TH1/TH2) using a multimeter.
- 2
2. Check for loose screw terminals, corrosion, or signs of overheating at both the motor and drive connection points.
- 3
3. Measure the resistance of the thermistor directly at the motor leads; compare to specified resistance-temperature curve if available.
- 4
4. Inspect the thermistor wires for physical damage, pinching, or breaks along the entire cable run.
- 5
5. Ensure the correct thermistor input type is selected in drive parameters (e.g., L1-01 for thermistor input selection, PTC or NTC).
- 6
6. If the thermistor and wiring are confirmed good, replace the drive if the fault persists.