DC Undervoltage

DC Bus Undervoltage

Yaskawa · V1000

Was bedeutet DC Undervoltage ?

The voltage on the internal DC bus has fallen below the minimum detection level (L2-05). This usually indicates a failure of the main power supply, a lost input phase, or an insufficient power supply capacity to meet the drive's demands. This condition causes the drive to shut down or operate erratically.

Häufige Ursachen

  • Loss of one or more incoming AC power phases (e.g., L1, L2, L3) or an excessive voltage sag in the main power supply.
  • Tripped upstream circuit breaker, blown input fuse(s), or loose connections on the drive's input terminals (L1, L2, L3).
  • Insufficient incoming AC voltage (e.g., below 380V for a 400V class drive) due to undersized transformer or utility brownout.
  • DC bus charge circuit fault (related to ref=72) preventing the bus capacitors from charging adequately.
  • Drive's internal rectifiers or DC bus capacitors are failing, leading to inability to maintain voltage.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Measure the incoming AC line voltage (L1-L2, L2-L3, L3-L1) at the drive's input terminals with a multimeter to ensure all phases are present and within the drive's specified voltage range (e.g., 400-480VAC).

  2. 2

    2. Inspect all power wiring connections from the main breaker/disconnect to the drive's input terminals (L1, L2, L3) for tightness, corrosion, or signs of damage.

  3. 3

    3. Check all upstream fuses and circuit breakers for continuity or trip status. Replace blown fuses with correct ratings, reset tripped breakers.

  4. 4

    4. Monitor the DC bus voltage (U1-03) during power-up to observe its charging behavior. Compare it to the minimum detection level (e.g., parameter L2-05).

  5. 5

    5. If the supply voltage is intermittently low, investigate the upstream power supply (e.g., transformer taps, utility voltage stability) to ensure adequate power capacity.

  6. 6

    6. For persistent undervoltage with good input power, the internal rectifier or DC bus capacitor bank may be failing, requiring drive repair or replacement.

Alle Codes in diesem Handbuch durchsuchen (87)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026