8002

POWERLINK error code (_ecPOWERLINK_ERROR)

ABB · ACS850 Standard Program Firmware

What does 8002 mean?

This is a general POWERLINK error code, meaning the POWERLINK master received an error from the drive. The specific fault is represented by a Profile Code in the Mint WorkBench Error Log, which requires hexadecimal conversion for proper identification. Unresolved POWERLINK errors disrupt real-time communication, making the drive unresponsive or causing system halts.

Common Causes

  • POWERLINK Master receiving a specific error code from the slave device (drive) indicating an application layer issue.
  • Mismatch in POWERLINK configuration (XDC file) between the Master and the actual slave device.
  • Slave device unable to achieve or maintain the configured POWERLINK state (e.g., Pre-operational, Operational).
  • Timing violations on the POWERLINK network, causing the slave to report errors (e.g., Master cycle time too fast).
  • Hardware failure on the slave device's POWERLINK communication interface.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Retrieve the specific POWERLINK Profile Code from the Mint WorkBench Error Log or the POWERLINK Master's diagnostic interface.

  2. 2

    2. Consult the POWERLINK specification and the drive's documentation for the meaning of the retrieved Profile Code.

  3. 3

    3. Verify the POWERLINK Master's configuration (XDC file) against the slave device's capabilities and current firmware.

  4. 4

    4. Inspect the POWERLINK network cabling (e.g., CAT5e/CAT6) and connections for damage or looseness.

  5. 5

    5. Monitor the POWERLINK status LEDs on the drive and Master to observe state transitions and error indications.

  6. 6

    6. Adjust the POWERLINK Master's cycle time or watchdog settings (if configurable) to address potential timing issues.

Browse all codes in this manual (57)
Verified technical data. Last updated: March 2026

Related Faults

Source: ABB ACS850 Standard Program Firmware