What does 16147 mean?

A checksum verification failed for data within the safety I/O module. This indicates data corruption in the safety configuration, I-Parameters, or F-Parameters, which are critical for the module's safe operation. This is a severity 3 error.

Common Causes

  • Data integrity check for the I/O module has failed.
  • Corrupted firmware or configuration data within the I/O module.
  • Memory error during data storage or retrieval.
  • Communication error affecting data transmission to the I/O module.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the overall safety configuration loaded into the I/O module.

  2. 2

    Verify the CRCs (Cyclic Redundancy Checks) for all I-Parameters and F-Parameters within the safety application.