28673

F-device Invalid Safety Destination Address (V3 CPU)

ABB · PB610 Panel Builder 600 Programming Software

What does 28673 mean?

The safety destination address (F_Dest_Add) for F-device instance <n> in an AC500 V3 non-safety CPU PM56xx system is not valid. This is a critical configuration error preventing safe PROFIsafe communication.

Common Causes

  • The F-device's safety destination address is invalid or not configured correctly.
  • Incorrect assignment of safety addresses within the PROFIsafe network configuration.
  • Conflicting safety destination addresses.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the Safety PLC configuration for F-device instance <n>.

  2. 2

    Verify or change the switch address setting to a valid F_Dest_Add.

  3. 3

    Restart the Safety PLC.

Browse all codes in this manual (58)
Verified technical data. Last updated: March 2026

Related Faults

Source: ABB PB610 Panel Builder 600 Programming Software