E4-9736

Hot Swap Terminal Unit Not Found

ABB · System

What does E4-9736 mean?

The system requires a hot swap terminal unit for proper operation, but it was not detected or is missing. This configuration error can prevent the system from recognizing or communicating with I/O modules, leading to incomplete system functionality or a halt.

Common Causes

  • The hot swap terminal unit is physically missing from the I/O rack or backplane assembly.
  • Loose, damaged, or unseated backplane connection between the hot swap terminal unit and the adjacent modules or controller.
  • Defective hot swap terminal unit hardware (e.g., failed communication interface, faulty detection circuitry).
  • Incorrect addressing (e.g., DIP switch settings P_ADDR_HEX) or configuration of the terminal unit in the PLC software.
  • System firmware or hardware configuration expects a hot swap unit, but a non-hot swap backplane is installed.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Physically verify the presence and proper installation of the hot swap terminal unit in its designated rack slot.

  2. 2

    2. Check the backplane connector pins for damage, corrosion, or debris between the terminal unit and adjacent modules.

  3. 3

    3. Verify that the hot swap terminal unit's address switches (if any) match the configured address (e.g., P_BUS_ADDR) in PLC software.

  4. 4

    4. Perform a controlled power cycle of the entire I/O rack or system controller.

  5. 5

    5. If possible, swap the suspected faulty hot swap terminal unit with a known good spare unit.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026