ABB · AC500-S Safety Controller
The PROFIsafe watchdog timer has expired, meaning the safety communication between the I/O module and the Safety PLC was not received within the expected timeframe. This indicates a loss of safety communication and will halt safe operations.
Click steps to track your progress.
Inspect all PROFIBUS/PROFINET cables and connectors (e.g., X1, X2 ports) between the Safety PLC and the I/O module for damage, looseness, or improper shielding.
Analyze network traffic and overall bus load using a network analyzer to identify excessive data volume or communication delays affecting PROFIsafe telegrams.
Verify the configured F-monitoring time (PROFIsafe watchdog time, e.g., Parameter F-MON) in the Safety PLC's safety program or I/O module's configuration matches the network's expected performance, potentially increasing it with careful risk assessment.
Temporarily power cycle the I/O module and the Safety PLC to reset their communication interfaces and clear any transient states.
Check for and address any other communication errors (e.g., 'PROFIsafe communication error' Code 20) that might be preceding the watchdog timeout, as they could be root causes.