E3-26

Parameter Value / Configuration Data Read Error

ABB · AC500-S Safety Controller

What does E3-26 mean?

This code indicates either an issue with a parameter value (potentially in the master or configuration) or that the Safety PLC cannot read its configuration data. Both scenarios prevent the PLC from operating correctly, potentially due to incorrect settings or data corruption.

Common Causes

  • Corrupted configuration data or parameter values stored in the safety PLC's non-volatile memory or on a connected safety I/O module.
  • Intermittent communication errors between the Safety PLC and its memory module (if applicable) or between the Safety PLC and an I/O module during configuration data transfer.
  • Firmware bug or hardware defect within the Safety PLC preventing proper reading of its own configuration data or external module parameters.
  • Power supply instability (e.g., voltage sags below 21.6VDC or transients) causing data corruption during write or read operations to/from memory.
  • An incorrect or incompatible safety configuration file loaded into the Safety PLC, leading to invalid parameter values or data structures.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Connect to the Safety PLC via engineering software and attempt to perform an "upload from device" to retrieve the current configuration; check for any reported inconsistencies or read errors.

  2. 2

    2. Re-download the last known good safety project configuration from the engineering workstation to the Safety PLC and any associated safety I/O modules.

  3. 3

    3. Verify the stability of the 24VDC control power supply to the Safety PLC using a multimeter, ensuring it remains within the specified voltage range (e.g., 21.6VDC to 26.4VDC).

  4. 4

    4. Replace the memory card (if removable) in the Safety PLC with a new one, then re-download the boot project and the complete safety application.

  5. 5

    5. If the error persists after re-downloading and verifying power supply, consider replacing the Safety PLC CPU module.

Browse all codes in this manual (48)
Verified technical data. Last updated: April 2026