ABB · AC500
A transmission error occurred, specifically indicating data inconsistency (CRC2 error) during PROFIsafe communication. This suggests corruption or incorrect data during transmission, which is critical for maintaining safety integrity.
Click steps to track your progress.
Inspect the PROFIsafe communication cable for physical damage and ensure proper shielding termination at both ends.
Check for strong sources of EMI near the PROFIsafe communication lines (e.g., unshielded motor cables, welding equipment).
Verify the configured PROFIsafe parameters, especially F_CRC_Length and F_WD_Time, for consistency between all safety devices.
Power cycle both the safety PLC and the associated safety I/O device.
Perform a cable test (e.g., continuity, attenuation) on the PROFIsafe communication line if possible.
Swap the suspected faulty PROFIsafe device (PLC or I/O) with a known good unit for testing.