A transmission error due to a timeout occurred in PROFIsafe communication, meaning that the expected response was not received within the specified F_WD_Time or F_WD_Time_2 watchdog period. This can lead to a safety function interruption if communication is critical.
Click steps to track your progress.
1. Check the physical integrity and secure connection of the PROFIBUS/PROFINET cable at both ends of the segment.
2. Verify that the bus termination resistors are correctly installed and switched 'ON' at the bus segment's start and end points.
3. Using a network diagnostic tool, check the PROFIBUS/PROFINET network for telegram errors, retransmissions, or missing frames.
4. Review and potentially increase the F_WD_Time or F_WD_Time_2 watchdog parameters in the safety configuration.
5. Isolate the suspected faulty module (safety PLC or safety I/O) by temporarily swapping it with a known good unit (if available).