ABB · AC500
The 'F_CRC_Length' parameter configured for PROFIsafe communication does not match the CRC length value generated internally by the device. This inconsistency in CRC configuration will lead to failed CRC checks, causing communication errors and compromising the integrity of safety data. Reliable safety communication cannot be established under these conditions.
Click steps to track your progress.
Access the PROFIsafe communication parameters in the PLC programming software for both the safety PLC and the connected safety I/O device.
Ensure that the F_CRC_Length parameter (e.g., CRC1, CRC2) is identically configured on both ends of the PROFIsafe communication link.
Consult the documentation for the specific safety devices to determine the recommended or default F_CRC_Length value.
Recompile the safety PLC project and download the updated configuration to all affected safety devices.
Verify network communication using diagnostic tools to check PROFIsafe telegram integrity.