The safety CPU fails to enter RUN mode after power-on, with the DIAG LED on and no boot project loaded. This often occurs if the power-off to power-on pause is less than 1.5 seconds, triggering a power dip detection that prevents the existing boot project from loading.
Click steps to track your progress.
Power off the safety CPU completely (remove 24VDC supply) and wait for a minimum of 5 seconds before re-applying power.
Download the complete safety PLC project, including the boot-up parameters, to the safety CPU.
Verify the integrity and correct insertion of the memory card (if applicable) into the CPU's slot.
Check the CPU's diagnostic buffer via the PLC programming software for specific boot-related error messages.
If the issue persists, replace the safety CPU module with a new, programmed unit.