EL
ErrorLib
Brands
||
  1. Home
  2. ABB
  3. ACS880-31 Hardware
  4. FA81
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

FA81

Safe Torque Off (STO) Channel Mismatch

ABB · ACS880-31 Hardware

What does FA81 mean?

This fault indicates a discrepancy in the status of the two Safe Torque Off (STO) channels. The drive's diagnostics have detected that the STO channels are not in the same state, or that STO was attempted to be activated in a non-redundant manner (e.g., only one channel activated). This prevents the STO safety function from operating correctly and will cause the drive to trip, leading to an uncontrolled stop or inability to start, posing a safety risk if machine motion is not reliably prevented.

Common Causes

  • The requested parameter identifier does not exist in the device's memory map.
  • Attempt to read or write to a non-existent parameter address.
  • Configuration mismatch between software and hardware parameter definitions.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify that both STO channels are receiving the correct and synchronous control signals from the safety controller. Inspect wiring and connections for integrity and proper termination.

  2. 2

    Review the logic and timing of the external safety system or controller that commands the STO function, ensuring both channels are activated and deactivated simultaneously.

  3. 3

    Check parameter 31.22 (STO fault/warning indication delay) in the drive's control program to understand the timing of fault detection and confirm it aligns with system expectations.

  4. 4

    If the issue persists after verifying external control and wiring, consult the drive's firmware manual for advanced diagnostics related to STO indications and internal status.

  5. 5

    If troubleshooting does not resolve the fault, contact ABB support as this may indicate an internal STO circuit failure within the drive that requires specialized attention.

Browse all codes in this manual (2)
Verified technical data. Last updated: April 2026

Related Faults

FA82Safe Torque Off (STO) Channel Mismatch
Source: ABB ACS880-31 Hardware
View Official PDFSearch more codes in this manual