ABB · ACS880
This event code is reserved and not actively used by the system for application events. Its appearance suggests that an unassigned event ID was triggered or a placeholder is being used inadvertently. Encountering this indicates a potential misconfiguration within the event generation logic.
Click steps to track your progress.
1. Identify the specific function block or code section attempting to trigger the '0x0001' event ID within the PLC program.
2. Review the event ID configuration within the drive's parameter settings (e.g., P10-01) to ensure no user-defined events are inadvertently mapped to this reserved ID.
3. Update the drive controller's firmware to the latest stable version, as a known bug might exist in older releases.
4. Modify the PLC program to use a valid, user-definable event ID (e.g., in the range 0xE000-0xEFFF) for custom events.