ABB · Application Error ABB Motion Drives Error trouble shoo
The drive has detected that its output frequency exceeded 550 Hz. This restriction is implemented to comply with relevant European Export Control Regulations, indicating an attempt to operate beyond a regulatory limit.
Click steps to track your progress.
Review the application's speed requirements and ensure that the commanded frequency does not exceed 550 Hz.
Check drive parameters related to maximum output frequency and adjust them to be below or equal to 550 Hz.
Verify scaling factors, gear ratios, and other motion parameters to ensure accurate calculation of output frequency.
Examine the external control system (e.g., PLC, HMI) to ensure it is not issuing commands that result in exceeding the 550 Hz limit.