EL
ErrorLib
Brands
||
  1. Home
  2. ABB
  3. Application Error ABB Motion Drives Error trouble shoo
  4. 8000
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

8000

EtherCAT AL status code

ABB · Application Error ABB Motion Drives Error trouble shoo

What does 8000 mean?

This error is reported along with a Profile Code in the Mint WorkBench Error Log. The displayed profile code must be converted to hexadecimal to reveal the specific EtherCAT error code. This status indicates that the EtherCAT master has received an error code from the drive (e.g., MotiFlex e100, MotiFlex e180, MicroFlex e190).

Common Causes

  • An underlying EtherCAT-specific error reported by the drive to the master.
  • Mismatch in EtherCAT configuration parameters between the master and the drive.
  • Issues with EtherCAT communication cables or network components (e.g., switches, couplers).
  • Invalid or unsupported EtherCAT object dictionary entries being accessed.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Connect to the drive with Mint Workbench and check the Error Log to obtain the associated Profile Code.

  2. 2

    Convert the displayed Profile Code from decimal to hexadecimal format to identify the specific EtherCAT error code.

  3. 3

    Consult the EtherCAT specification or the drive's EtherCAT documentation for the meaning of the specific hexadecimal error code.

  4. 4

    Verify the EtherCAT network cabling and connections for integrity, proper termination, and shielding.

  5. 5

    Check the EtherCAT configuration settings on both the master and the drive for consistency and correctness.

Browse all codes in this manual (58)