ABB · PB610 Panel Builder 600 Programming Software
The PROFIsafe watchdog for F-device instance <n> with AC500 V3 non-safety CPU PM56xx has timed out. This indicates that safety communication telegrams are not being received within the expected time, potentially due to communication issues or an incorrectly configured watchdog timer.
Click steps to track your progress.
Restart the affected F-device module.
Increase the PROFIsafe watchdog time parameter in the Safety PLC configuration.