3

Discrepancy time expired

ABB · PB610 Panel Builder 600 Programming Software

What does 3 mean?

The time difference between input signals from redundant sensors connected to a safety I/O module has exceeded the configured discrepancy time limit. This indicates a potential issue with sensor synchronization, signal integrity, or incorrect timing configuration. This is a severity 3 error.

Common Causes

  • Expected synchronization pulse not received within the allowed timeframe.
  • Communication delay between master and slave devices.
  • Clock drift between synchronized components.
  • Intermittent communication errors on the bus.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the configured discrepancy time value within the safety application or module parameters.

  2. 2

    Verify the physical wiring of the affected safety channel, ensuring connections are secure and correct.

  3. 3

    Inspect the sensors connected to the channel for proper operation, alignment, and response time.