ABB · System
The required process voltage (UP or UP3) for the I/O bus module is not present. This critical power supply issue will prevent the I/O module and any connected field devices from operating correctly, resulting in a complete loss of I/O functionality.
Click steps to track your progress.
1. Measure the voltage at the UP and UP3 input terminals of the I/O module (relative to COM) using a multimeter.
2. Inspect and test all fuses (e.g., F1, F2) on the power distribution block supplying the I/O module.
3. Disconnect all external field devices from the I/O module and re-measure the UP/UP3 voltage.
4. Verify the output voltage of the external power supply unit (e.g., 24VDC PSU) feeding the UP/UP3 rail.
5. Check for short circuits or open circuits in the wiring between the power supply and the I/O module's terminals.