ABB · System
The system's battery is either empty or entirely missing. This warning indicates that non-volatile data, such as configuration parameters, retained variables, or real-time clock settings, may be lost during power cycles if the issue is not resolved. This can lead to system re-configuration needs on every restart.
Click steps to track your progress.
1. Locate the battery compartment on the module (e.g., under a front cover, on the main board).
2. Measure the voltage of the installed battery using a multimeter (e.g., expect ~3V for a new CR2032). If below 2.5V, it is depleted.
3. Carefully remove the old battery, inspect the battery holder for corrosion or bent contacts, and clean them with a contact cleaner or small brush.
4. Install a new, manufacturer-specified battery (e.g., CR2032 lithium primary cell, specifying voltage and capacity) with correct polarity.
5. After battery replacement, power cycle the module and re-enter any non-volatile parameters (e.g., Real-Time Clock, specific retain values) that might have been lost.