Allen-Bradley · 160
This fault indicates that the DC Bus voltage has remained below 85% of its nominal value for more than 5 seconds during power-up. It points to an issue with the incoming AC supply, potentially leading to unstable operation or damage if the controller attempts to operate with insufficient power.
Click steps to track your progress.
1. Measure AC line voltage at the controller's L1, L2, L3 input terminals during power-up using a multimeter (e.g., Fluke 179). Verify voltage matches nameplate rating (e.g., 400V AC +/-10%).
2. Inspect all input fuses (e.g., F1, F2, F3) for continuity using a multimeter; replace any open fuses with specified type and rating.
3. Check continuity of the AC input cabling from the main disconnect to the controller's L1, L2, L3 terminals. Tighten all terminal screws to specified torque.
4. Monitor the DC bus voltage (e.g., at terminals P+, N-) during power-up using a DC voltmeter. Compare to expected nominal value (e.g., 560V DC for 400V AC input).
5. Verify the upstream circuit breaker or contactor is closed and rated appropriately for the drive's FLA (Full Load Amps).