F33

AutoRstrt Tries

Allen-Bradley · PowerFlex 4 Adjustable Frequency

What does F33 mean?

This fault indicates that the drive has reached the maximum configured number of automatic restart attempts (set by parameter A092 [AutoRstrt Tries]) after a preceding fault. This signifies a persistent underlying fault condition that requires manual intervention.

Common Causes

  • Drive attempted to restart after a transient fault multiple times.
  • Persistent motor load or control issue preventing stable operation.
  • Configuration parameter P0-05 set for automatic restarts.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Identify and correct the root cause of the previous fault condition that triggered the auto-restart attempts.

  2. 2

    Manually clear the fault by pressing the Stop key on the keypad, cycling power to the drive, or setting parameter A100 [Fault Clear] to option 1 ('Reset Fault') or 2 ('Clear Buffer').

  3. 3

    Review and adjust parameter A092 [AutoRstrt Tries] if the number of restart attempts is inappropriate for the application.

Browse all codes in this manual (24)
Verified technical data. Last updated: March 2026