F48
Params Defaulted
Allen-Bradley · PowerFlex 4 Adjustable Frequency
What does F48 mean?
This fault indicates that the drive has either been commanded to restore factory default values to its EEPROM, or a corruption of parameter data occurred spontaneously. This resets all configurable parameters.
Common Causes
- Power loss or incorrect parameter save operation.
- Factory reset or parameter initialization performed.
- EEPROM or memory corruption affecting parameter storage.
- Parameter load failure from external source.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Clear the fault by pressing the Stop key, cycling power to the drive, or setting parameter A100 [Fault Clear] to option 1 ('Reset Fault') or 2 ('Clear Buffer').
- 2
Reprogram all necessary drive parameters to their application-specific values after the defaults have been written.
Verified technical data. Last updated: March 2026
Related Faults
Source: Allen-Bradley PowerFlex 4 Adjustable Frequency