F082

Opt Comm Loss

Allen-Bradley · PowerFlex 520-series Adjustable Frequency

What does F082 mean?

Communications between the drive and its installed network option card have been interrupted. This indicates a problem with the internal data exchange between the main drive controller and the optional network interface card itself, affecting remote connectivity and control. The drive's response to this loss is defined by parameter C125 [Comm Loss Action].

Common Causes

  • Network option card (e.g., EtherNet/IP, DeviceNet) not fully seated in the drive's option slot.
  • Corruption of the option card's firmware or internal configuration settings.
  • Failure of the internal communication bus between the drive's main control board and the option card.
  • Power supply issue to the option card internally within the drive.
  • Incorrectly configured parameters related to the option card's operation (e.g., P8-xx for network-specific settings).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Power down the drive completely, then remove and re-seat the network option card into its slot, ensuring firm contact.

  2. 2

    2. Check drive status and fault logs for additional diagnostic information related to option card initialization failures.

  3. 3

    3. If a spare option card is available, replace the existing card and retest drive operation.

  4. 4

    4. Verify that drive firmware and option card firmware versions are compatible according to manufacturer documentation.

  5. 5

    5. Reset option card parameters to factory defaults (if supported by a specific parameter, e.g., P8-10 = 0) and reconfigure necessary settings.

Browse all codes in this manual (48)
Verified technical data. Last updated: March 2026

Related Faults

Source: Allen-Bradley PowerFlex 520-series Adjustable Frequency