F106

Incompat C-P

Allen-Bradley · PowerFlex 520-series Adjustable Frequency

What does F106 mean?

The PowerFlex 525 control module has been paired with a power module that has an incompatible 0.25 HP power rating, which it does not support. This is a fundamental hardware mismatch between the control and power sections, preventing proper operation.

Common Causes

  • A PowerFlex 525 control module is paired with a power module whose nameplate indicates a 0.25 HP rating, which is not supported by the 525 series.
  • Incorrect power module was physically installed with a PowerFlex 525 control module (e.g., mixing PowerFlex 523 power section with 525 control).
  • The power module's internal identification (ID) chip or circuitry is reporting an incorrect or corrupted HP rating to the control module.
  • Firmware mismatch where the control module's firmware does not properly recognize the ID of certain power module variants.
  • Damage to the communication interface between the control module and the power module, causing misinterpretation of the power module's ID.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify the exact catalog number and HP rating on the nameplate of the power module against the specifications for the PowerFlex 525 drive series.

  2. 2

    2. Ensure the installed power module is indeed a PowerFlex 525 series power module and not a different PowerFlex 500 series variant (e.g., 523, 527).

  3. 3

    3. If the power module is confirmed to be incorrect, replace it with a compatible PowerFlex 525 series power module of the correct HP rating.

  4. 4

    4. Power down the drive, remove the control module, inspect its connectors for damage, and re-seat it firmly onto the power module.

  5. 5

    5. Record the firmware revision of the control module and check for any manufacturer bulletins regarding power module compatibility issues.

Browse all codes in this manual (48)
Verified technical data. Last updated: March 2026

Related Faults

Source: Allen-Bradley PowerFlex 520-series Adjustable Frequency