79
Excessive Load
Allen-Bradley · PowerFlex 700
What does 79 mean?
The motor did not come up to speed in the allotted time during an autotune procedure. This indicates the motor or connected load is preventing the autotune from completing successfully, potentially due to high friction or an oversized load.
Common Causes
- Mechanical system connected to the drive is experiencing a high load.
- Application demanding more torque than the motor can deliver.
- Incorrect motor sizing for the application.
- Faulty coupling or gearbox causing increased drag.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Uncouple the mechanical load from the motor.
- 2
Repeat the Autotune procedure.
Verified technical data. Last updated: March 2026
Related Faults
Source: Allen-Bradley PowerFlex 700