Allen-Bradley · Compact 5000 I/O Serial Module
This boolean tag indicates that a buffer overrun occurred within the Modbus slave module's ASIC (Application-Specific Integrated Circuit) during data reception. A value of 1 (Occurrence) means the slave's receive buffer overflowed because incoming data arrived too quickly to be processed. This condition can lead to data loss and unreliable slave operation.
Click steps to track your progress.
Reduce the baud rate setting in the module's configuration to allow the ASIC more time to process incoming data.
Ensure the Modbus master is not sending data at an excessively high rate or with insufficient delays between messages.
Verify the slave module's firmware is current to ensure optimal data handling and buffer management.