Allen-Bradley · Compact 5000 I/O Serial Module
This boolean tag indicates that a CRC (Cyclic Redundancy Check) or LRC (Longitudinal Redundancy Check) error occurred during Modbus slave communication. A value of 1 (Occurrence) means that the received Modbus message failed its integrity check, suggesting data corruption during transmission. This indicates an issue with the physical layer or data format.
Click steps to track your progress.
Inspect the serial communication cable for physical damage, proper shielding, and correct termination (e.g., 120 ohm resistors at ends of bus).
Verify the Modbus master's CRC/LRC calculation method and settings match the slave module's expected method.
Check for external sources of electromagnetic interference (EMI) affecting the communication line and implement mitigation measures.
Measure the signal integrity on the Modbus communication lines using an oscilloscope to identify noise or signal degradation.