I xx .Command yy .ResponseTimeout

Modbus Master Command Response Timeout

Allen-Bradley · Compact 5000 I/O Serial Module

What does I xx .Command yy .ResponseTimeout mean?

This boolean tag indicates that the Modbus master did not receive a response from the slave device within the configured timeout period after sending a specific Modbus command (Command yy). A value of 1 (Occurrence) means the command failed to complete due to the slave's unresponsiveness. This can halt data exchange for that command.

Common Causes

  • Modbus slave device is offline, unpowered, or non-responsive
  • Incorrect slave address configured for Command yy in the module's command list
  • Physical communication line break or severe network congestion
  • Timeout value set too low in the module's configuration for the slave's response time

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the Modbus slave device is powered on, operational, and correctly addressed.

  2. 2

    Check the configured Modbus slave address for Command yy matches the physical slave device's address.

  3. 3

    Inspect the serial communication cable for continuity and proper termination.

  4. 4

    Increase the Modbus command timeout value in the module's configuration if slave response times are slow or variable.

Browse all codes in this manual (28)