This boolean tag indicates if a connection between the module and its owner-controller is not running. A value of 1 signifies that the connection is faulted or not established. A value of 0 indicates the connection is running normally. This fault prevents the module from exchanging data with the controller.
Click steps to track your progress.
Verify the module configuration in the Logix Designer application, ensuring it matches the physical module and is complete.
Confirm the controller's operational mode is Remote Run or Run mode.
Inspect the network cable connected to the module for damage or loose connections.
Check if the module is inadvertently inhibited in the Logix Designer application and un-inhibit if necessary.