This fault indicates that the Control Variable (CV) health is bad. This can be due to poor CV value quality, an invalid CV value, or a communication fault affecting the CV output. When true, CVFault indicates an error on the output module, and the PIDE instruction sets the appropriate bit in Status. The equivalent Sts_CVBad in the PPID instruction will also be set if Inp_CVIOFault is true.
Click steps to track your progress.
Verify the analog output signal from the CV output module (e.g., terminals) using a multimeter or process calibrator
Check the communication status of the CV output module in the I/O tree, looking for module faults
Confirm the CV output module is healthy and not reporting internal faults via its diagnostics
Verify that the Inp_CVIOFault input (for PPID) is not actively being driven high by external conditions or logic