Allen-Bradley · PowerFlex 4 Adjustable Frequency
A grounded phase condition has been detected specifically on motor phase U or in the wiring connecting drive output terminal U to the motor. This indicates a direct short path to ground.
Click steps to track your progress.
Disconnect the motor from the drive output terminals (U, V, W).
Measure insulation resistance between drive output terminal U and earth ground using a megger at 500VDC; expect a reading greater than 1 MΩ.
Measure insulation resistance between motor phase U and the motor frame using a megger at 500VDC; expect a reading greater than 1 MΩ.
Inspect the wiring connecting drive output terminal U and motor phase U for any physical damage or signs of insulation breakdown.