A grounded phase condition has been detected specifically on motor phase V or in the wiring connecting drive output terminal V to the motor. This indicates a direct short path to ground.
Click steps to track your progress.
Disconnect the motor from the drive output terminals (U, V, W).
Measure insulation resistance between drive output terminal V and earth ground using a megger at 500VDC; expect a reading greater than 1 MΩ.
Measure insulation resistance between motor phase V and the motor frame using a megger at 500VDC; expect a reading greater than 1 MΩ.
Inspect the wiring connecting drive output terminal V and motor phase V for any physical damage or signs of insulation breakdown.