F40

Phase W to Gnd

Allen-Bradley · PowerFlex 4 Adjustable Frequency

What does F40 mean?

A grounded phase condition has been detected specifically on motor phase W or in the wiring connecting drive output terminal W to the motor. This indicates a direct short path to ground.

Common Causes

  • Phase W winding shorted to ground in the motor.
  • Cable insulation failure between phase W and ground.
  • Internal drive fault with phase W output stage.
  • Grounding fault on phase W line conductor.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect the motor from the drive output terminals (U, V, W).

  2. 2

    Measure insulation resistance between drive output terminal W and earth ground using a megger at 500VDC; expect a reading greater than 1 MΩ.

  3. 3

    Measure insulation resistance between motor phase W and the motor frame using a megger at 500VDC; expect a reading greater than 1 MΩ.

  4. 4

    Inspect the wiring connecting drive output terminal W and motor phase W for any physical damage or signs of insulation breakdown.

Browse all codes in this manual (24)
Verified technical data. Last updated: April 2026